| Specifications |
| PartNumber | E5CS- 1KJX | E5CS-1PX | E5CS- 1GX |
| SensorInput Device | ThermocoupleType J (IC) and Type K (CA) | Platinum RTD(Pt:100W ) DIN orJIS standard | Thermistor (interchangeable type) |
| Supplyvoltage | 100to 240 VAC, 50/60 Hz; operates on 85 to 110% of rated voltage |
| Powerconsumption | Approx.7 VA |
| Controloutput | Contact | Type | SPDTrelay |
| Max. load | 3A,250 VAC (resistive load) |
| Voltage | Logic load | 12VDC, 20 mA with short-circuit protection |
| Hysteresis | 0.2%of full scale during ON/OFF control action |
| Responsetime | Output | 2seconds for output to change |
| Display | 2seconds for displayed indication to change |
| Service life | MechanicalElectrical | 10million operations minimum with contact output 100,000 operation minimum with contactoutput |
| Alarmoutput | Type | SPST� NO relay |
| Max. load | 1A, 250 VAC (resistive load) |
| Setting range | Absolutevalue alarm: Same as control output setting range Other: 0 to full scale |
| Settingaccuracy | Setvalue coincides with indicated value, so no relative error exists |
| Indicationaccuracy | ±0.5% of full scale, ±1 digit max. |
| Controlmodes | Type | ON/OFFand PID with automatic tuning if proportional band, switch selectable |
| Proportionalband | 3to 20% (in PID mode) automatically adjusted according to the rise timeof the controlled system |
| Resettime | 4minutes (in PID mode) |
| Ratetime | 0.4minutes (in PID mode) |
| Proportionalperiod | 2of 20 seconds, switch selectable |
| Samplingperiod | 500ms |
| Approvals | UL | Recognized,File number E68481 |
| CSA | Certified,File number LR59623 |
| Ambienttemperature | Operating | -10°to 55° C (-14°to 131° F) |
| Storage | -25°to 65° C ( -13°to 149° F) |
| Humidity | 35to 85% RH |
| Insulationresistance | 20MW minimum at 500VDC |
| Dielectricstrength | 2,000VAC, 50/60 Hz for 1 minute between current-carrying terminals of differentpolarity |
| Vibration | Mechanicaldurability | 10to 55 Hz, 0.75 mm (0.03 in) double amplitude in X,Y, and Z directions for2 hours each |
| Malfunctiondurability | 2to 55 Hz, 2 G in X,Y, and Z directions for 10 minutes each |
| Shock | Mechanicaldurability | 30m/s²,in 6 directions, 3 times each |
| Malfunctiondurability | 100m/s², in 6 directions, 3 times each |