E5EF Fuzzy Temperature Controls

1/8 DIN Controller combine FRZZY and PID control for fast response to process disturbances.

Features

  • Advanced PID control for optimal response during start-up and steady-state operation
  • FUZZY and PID control work together to correct a process upset quickly, with minimal overshoot
  • FUZZY parameters can be changed to adjust fuzzy control�s impact on the process
  • Accuracy to 0.3% of set value
  • Field-selectable temperature ranges, F/ C scaling, and sensor input types
  • Plug-in outputs for field interchangeability
  • Communications function, heater burnout alarm and 8-bank model available
  • 3-year warranty

 

Specifications

Order one control output separately below. For example, E5EF-A02TC-F with E53-S SSR output unit. For heater burnout models, be sure to order a current transformer. To order models marked for degrees Celsius, omit the "F" at the end of the part number.

Controller type

Standard

Heater burnout type*

Input type

Thermocouple(10 types)

Platinum RTD

Thermocouple (10 types)

Platinum RTD

No communications

E5EF-ATC-F

E5EF-AP-F

E5EF-AHTC-F

E5EF-AHP-F

RS-422 communications

E5EF-A02TC-F

E5EF-A02P-F

E5EF-AHO2TC-F

E5EF-AH02P-F

RS-485 communications

E5EF-A03TC-F

E5EF-A03P-F

E5EF-AH03TC-F

E5EF-AH03P-F

8-bank program memory

E5EF-BATC-F

E5EF-BAP-F

E5EF-BAHTC-F

E5EF-BAHP-F

* Current Output E53-C may not be used with heater burnout type controllers.

TEMPERATURE RANGES

Sensor input type

Thermocouple

 

Type K

Type J/L

Type T/U

Type E

Type R/S

Type B

Type N

Temperature

C

-200 to 1,300

-100 to 850

-200 to 400

0 to 600

0 to 1,700

100 to 1,800

0 to 1,300

range

F

-300 to 2,300

-100 to 1,500

-300 to 700

0 to 1,100

0 to 3,000

300 to 3,200

0 to 2,300

Unit of measure

1 C or F, main setting and alarm

Sensor input type

Platinum RTD (Pt100 or JPt100)

Temperature

C

-99.9 to 450.0

range

F

-99.9 to 800.0

Unit of measure

0.1 C or F, main setting and alarm

CONTROL OUTPUT UNITS

Output type

Relay

SSR

Voltage output (for driving SSR)

Current

 

output*

output

12 VDC (NPN)

24 VDC (NPN)

24 VDC (PNP)

output

Part number

E53-R

E53-S

E53-Q

E53-Q3

E53-Q4

E53-C

 

CURRENT TRANSFORMERS FOR HEATER-BURNOUT CONTROLLERS

Hole DIAMETER

5.8 mm (0.23 in.)

12.0 mm (0.47 in.)

Part number

E54-CT1

E54-CT3

* Note: If control period is less than 5 seconds, use solid state relay or voltage relay.